หม้อแปลงขนาด 100 KVA

หม้อแปลงขนาด 100 KVA

Rated  power ..……KVA 100
Type of  transformer  – Oil immersed ( Hermetically  sealed )
Standard  – IEC  76
Cooling  System  – ONAN
No. Of phase  – 3
Frequency ……….Hz 50
Rate  of  voltage       : Primary ……….V. 33000
                                 : Secondary ..………V. 400/230
Vector  group  – Dyn  11
Tapping         Type  – Off  Circuit  Tap  Changer
         No. of steps  – 5
         Percentage  of  tapping  –
 + 2 x 2.5 %
Impedance  voltage at 75 C ………..% 4
NO – Load current …..…..% 1
Ambient  temperature …..…….C 40
Average  Temperature  rise  of winding …..…….C 65
Average  Temperature  rise  of  top oil …………C 60
Noise level not more than ….……dB 56
No – Load loss ……..Watt 250
Load  loss  at  75 C ……..Watt 1550
: 25 %  of rate  power …….….% 98.94
Efficiency : 50 % of rate   power …………% 98.08
at  P.F. = 1 : 75 % of rate   power ………..% 98.79
: 100 % of rate power …..……% 98.56
Voltage  regulation : at  P.F.  = 0.8 …….….% 3.22
: at  P.F.  = 0.9 …….….% 2.71
: at  P.F.  = 1. ….…….% 1.17
Impulse Withstand : Primary  winding ..…….KV. 125
Voltage : Secondary winding ………KV.  –
Power  Frequency : Primary  winding ….…..KV. 50
: Secondary winding ………KV. 3
Terminal  arrangement H.V. Side Cable
 L.V. Side Cable
Installation  on Pole  mounted / Plantform