หม้อแปลงขนาด 3150 KVA

หม้อแปลงขนาด 3150 KVA

Rated  power..……KVA3150
Type of  transformer –Oil immersed ( Hermeticall  sealed  tank  )
Standard –IEC  76
Cooling  System –ONAN
No. Of phase –3
Frequency……….Hz50
Rate  of  voltage       : Primary……….V.22000
                                 : Secondary..………V.400/230
Vector  group –Dyn  11
Tapping        Type –Off  circuit  tap  changer
         No. of steps –
5
         Percentage  of  tapping –2 x 2.5 %
Impedance  voltage at 75 C………..%7
NO – Load current…..…..%3
Ambient  temperature…..…….C40
Average  Temperature  rise  of winding…..…….C65
Average  Temperature  rise  of  top oil…………C60
Noise level not more than….……dB56
No – Load loss……..Watt4100
Load  loss  at  75 C……..Watt33000
: 25 %  of rate  power…….….%99.42
Efficiency: 50 % of rate   power…………%99.22
at  P.F. = 1: 75 % of rate   power………..%90.04
: 100 % of rate power…..……%98.84
Voltage  regulation: at  P.F.  = 0.8…….….%3.22
: at  P.F.  = 0.9…….….%2.71
: at  P.F.  = 1.….…….%1.29
Impulse Withstand: Primary  winding..…….KV.125
Voltage: Secondary winding………KV. –
Power  Frequency: Primary  winding….…..KV.50
: Secondary winding………KV.3
Terminal  arrangement H.V. SideCable
 L.V. SideCable
Installation  onPole  mounted / Plantform