หม้อแปลงขนาด 3150 KVA

หม้อแปลงขนาด 3150 KVA

Rated  power ..……KVA 3150
Type of  transformer  – Oil immersed ( Hermeticall  sealed  tank  )
Standard  – IEC  76
Cooling  System  – ONAN
No. Of phase  – 3
Frequency ……….Hz 50
Rate  of  voltage       : Primary ……….V. 22000
                                 : Secondary ..………V. 400/230
Vector  group  – Dyn  11
Tapping         Type  – Off  circuit  tap  changer
         No. of steps  –
5
         Percentage  of  tapping  – 2 x 2.5 %
Impedance  voltage at 75 C ………..% 7
NO – Load current …..…..% 3
Ambient  temperature …..…….C 40
Average  Temperature  rise  of winding …..…….C 65
Average  Temperature  rise  of  top oil …………C 60
Noise level not more than ….……dB 56
No – Load loss ……..Watt 4100
Load  loss  at  75 C ……..Watt 33000
: 25 %  of rate  power …….….% 99.42
Efficiency : 50 % of rate   power …………% 99.22
at  P.F. = 1 : 75 % of rate   power ………..% 90.04
: 100 % of rate power …..……% 98.84
Voltage  regulation : at  P.F.  = 0.8 …….….% 3.22
: at  P.F.  = 0.9 …….….% 2.71
: at  P.F.  = 1. ….…….% 1.29
Impulse Withstand : Primary  winding ..…….KV. 125
Voltage : Secondary winding ………KV.  –
Power  Frequency : Primary  winding ….…..KV. 50
: Secondary winding ………KV. 3
Terminal  arrangement H.V. Side Cable
 L.V. Side Cable
Installation  on Pole  mounted / Plantform